CS2-PR-2008-05-14
C2-01-1
8
CS2-PR PROCESS Indicator
DESCRIPTION
CS2-PR Process Indicator has been designed with high
accuracy measurement, display and communication of DC
signal 0~10V and 4(0)~20mA with square root function
.
They are also build in 4 Relay outputs, 3 External Control
Inputs, 1 Analogue output and 1 RS485(Modbus RTU Mode)
interface with versatile functions such as control, alarm,
re-transmission and communication for a wide range of
industrial applications.
FEATURE
● Measuring linear signal 0~10V and 0(4)~20mA(with Square Root function) in one indicator(input
code: AV)
● 4 relay can be programmed individual to be a Hi / Lo / Hi Latch / Lo Latch / Go energized with
Start Delay / Hysteresis / Energized & De-energized Delay functions, or to be a remote control.
● Analogue output and RS 485 communication port in option
● 3 external control inputs can be programmed individual to be Relative PV (Tare) / PV Hold /
Maximum or Minimum Hold / DI (remote monitoring) / Reset for Relay Energized Latch….
● CE Approved & RoHS
ORDERING INFORMATION
CS2−PR−
Input
Signal
−
Relay
Output
−
Analogue
Output
−
RS 485
Port
−
Aux.
Powered
−
*Optional
Function
Customize function is welcome. Please contact with our sales window
for detail.
CODE INPUT RANGE CODE RELAY O/P CODE ANALOG O/P CODE RS485 PORT CODE AXU. POWER CODE FUNCTION
A1
0(4) ~ 20mA / 0 ~ 10mA
N
None
N
None
N
None
A
AC115/230V
V1
0 ~ 10V / 0(1) ~ 5V
R2
2 Relay
8
RS 485
SOP
Sensor Open
Protection
AV
0~10V/0~20mA(all in one)
R4
4 Relay
V
0(1) ~ 5 V
0 ~ 10 V
ADH*
AC/DC 85~264V
AO
Specify A input
ADL*
AC/DC 20~90V
SQR
Square root
function
VO
Specify V input
I
0 ~ 10 mA
4(0)~20 mA
Reading Stable Function
TECHNICAL SPECIFICATION
Average:
Settable range: 1~99 times
Input
Moving average:
Settable range: 1(None)~10 times
Digital filter:
Settable range: 0(None)/1~99 times
Input Range
Input
Impedance
Input Range
Input
Impedance
Voltage
0 ~ 10 V ≥ 1M ohm
Current
4
0
~20 m
250 ohm
Control Functions(option)
¾ The Meter can be 0~10V and 0~20mA in one unit
accordin
to connection
11 or #12
Set-points:
Four set-points
Control relay:
Four relays
Calibration:
Digital calibration by front key
Relay 2 & Relay 3: Dual FORM-C, 5A/230Vac, 10A/115V
A/D converter:
16 bits resolution
Relay 1 & Relay 4: Dual FORM-A, 1A/230Vac, 3A/115V
Accuracy:
≤± 0.04% of FS ± 1C;
Relay energized mode:
Energized levels compare with set-points:
Sampling rate:
15 cycles/sec
Hi / Lo / Go.12 / Go.23 / Hi.HLd / Lo.HLd; programmable
Response time:
≤100 msec.(when the AvG = “1”) in standard
DO function: Energized by RS485 command of master.
Input type:
0~10V / 0~5V / 1~5V / 0-10mA / 0~20mA / 4~20mA
Energizing functions:
Start delay / Energized & De-energized delay / Hysteresis /
programmable for coding AV(option)
Energized Latch
Input range:
Input High and Low programmable Start band(Minimum level for Energizing): 0~9999counts
Ai.Hi: Settable range: 0.00~100.00% of input range Start delay time: 0:00.0~9(Minutes):59.9(Second)
Ai.Lo: Settable range: 0.00~100.00% of input range
Energized delay time: 0.00.0~9(Minutes):59.9(Second)
De-energized delay time: 0.00.0~9(Minutes):59.9(Second)
Display & Functions Hysteresis: 0~5000 counts
LED:
Numeric: 5 digits, 0.8”(20.0mm)H red high-brightness LED
Relay output indication: 4 square red LED
External Control Inputs(ECI)
RS 485 communication: 1 square orange LED
Input mode:
3 ECI points, Contact or open collect input, Level trigger
E.C.I. function indication: 3 square green LED
Functions:
Relative PV(Tare) / PV Hold / Reset for Max or Mini. Hold /
Max/Mini Hold indication: 2 square orange LED
DI / Reset for Relay Energized latch
Display range:
-19999~29999;
Debouncing time:
Settable range 5 ~255 x (8m seconds)
Scaling function:
Lo.SC: Low Scale; Settable range: -19999~+29999
Hi.SC: High Scale; Settable range: -19999~+29999 Analogue output(option)
Decimal point:
Programmable from 0 / 0.0 / 0.00 / 0.000 / 0.0000
Accuracy:
≤
0.1% of F.S.; 16 bits DA converter
Square root function:
Selectable for differential pressure transducers
Ripple: ≤± 0.1% of F.S.
Over range indication:
ovFL, when input is over 120% of input range Hi
Response time:
≤100 msec. (10~90% of input)
Under range indication:
-ovFL, when input is under -20% of input range Lo
Isolation:
AC 2.0 KV between input and output
Max / Mini recording:
Maximum and Minimum value storage during power on.
Output range:
Specify either Voltage or Current output in ordering
Display functions:
PV / Max(Mini) Hold / RS 485 Programmable
Voltage: 0~5V / 0~10V / 1~5V programmable
Front key functions:
Up and down key can be set to be a function as ECI.
Current: 0~10mA / 0~20mA / 4~20mA programmable
Low cut:
Settable range: -19999~29999 counts Output capability:
Voltage: 0~10V: ≥ 1000Ω;
Digital fine adjust:
Pv.Zro: Settable range: -19999~+29999
Current: 4(0)~20mA: ≤ 600Ω max
Pv.SPn: Settable range: -19999~+29999
Amend: 2009/11/14; Add square root function
OPTION 2 OPTION 3OPTION 1
Excitation Supply DC24V in build for 2 wire transmitters
CSM-321S
CS2-
A
CSM-321S CSM-CSM-
CS2-PR
CSM-321S CSM-CSM-
CSM-321S CSM-
CSM-321S
OPTION 4 OPTION 4
OPTION 4