www.schneider-electric.com 1/4 S1A10942 - 04/2010
Quick Start Guide - ATV312
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this product.
Information below is designed to use single drive connected to single motor with a motor cable length less than 50 meters (164 ft).
In any other case, consult the ATV312 installation and programming manual on www.schneider-electric.com.
Check your cables before connecting the drive with motor (length, power, shielded or unshielded). Motor cable length is _______(< 50 meters, 164 ft)
Check the delivery of the drive
• Remove ATV312 from the packaging and check that it has not been damaged.
• Check that the drive reference printed on the label is the same as that on the delivery note corresponding to the
purchase order.
Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________
Check the line voltage compatibility
• Check that the line voltage is compatible with the supply range of the drive.
Line voltage _______ Volts / Drive voltage range _______ Volts
Drive range: ATV312
M2 = 200 ... 240 V single phase / ATV312 M3=200 ... 240 V three-phase
ATV312
N4 = 380 ... 500 V three-phase / ATV312 S6 = 525 ... 600 V three-phase
Mount the drive vertically
For a surrounding air temperature up to 50 °C (122 °F)
See installation manual on www.schneider-electric.com for other thermal conditions.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this quick start guide before performing any procedure with this drive.
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all
equipment.
• Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Before servicing the drive:
- Disconnect all power, including external control power that may be present.
- Place a "DO NOT TURN ON" label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
- Measure the voltage of the DC bus between the PA/+ and PC/- terminals to ensure that the voltage is less than 42 Vdc.
- If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or operate
the drive
• Install and close all covers before applying power or starting and stopping the drive.
Failure to follow these instructions will result in death or serious injury.
WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
8B0917121134
(a)
(a)
(a)
(a)
(a) 50 mm (2 in.)
(b)
10 mm (0.4 in.)
(b)