0x01 long status
49 setpoint humidity 10-90% 10..90 x x x x x
50 year 0..99 0..99 x x x x
51 month 1..12 1..12 x x x x
52 day 1..31 1..31 x x x x
53 hour 0..23 0..23 x x x x
54 minute 0..59 0..59 x x x x
55 return air temp. too high alarm 0..30°C 0..30 x x x x x
56 supply air temp. too high alarm 0..30°C 0..30 x x x
57 return air temp. too low alarm 0..30°C 0..30 x x x x x
58 supply air temp. too low alarm 0..30°C 0..30 x x x
59 water temp. too high alarm 0..50°C 0..50 x x x
60 water temp. too low alarm -50..+30°C 0..80 x x x
61 return air humid. too high alarm 0..90% 0..90 x x x x x
62 supply air humid. too high alarm 0..90% 0..90 x x x
63 return air humid. too low alarm 0..90% 0..90 x x x x x
64 supply air humid. too low alarm 0..90% 0..90 x x x
------------------------------------- d a t a m o d u l e 1 -----------------------------------------
65 compressor start (setpoint + val) 0.0..10.0 K 0..100 x x x x x
66 compressor hysteresis 0.0..10.0 K 0..100 x x x x x
67 suction valve start 0.0..10.0 K 0..100 x x x
68 suction valve proportional band 0.0..10.0 K 0..100 x x x
69 drycooler start temperature 0..45°C 0..45 x x x
70 drycooler enable temperature 0..45°C 0..45 x ?
71 glycol-pump start temperature 0.0..10.0 K 0..100 x x x
72 GE/CW valve off temperature 0..35°C 0..35 x x x
73 GE/CW valve start temperature 0.0..10.0 K 0..100 x x x x
74 GE/CW valve proportional band 0.0..10.0 K 0..100 x x x x
75 reheat 1 start temperature 0.0..10.0 K 0..100 x x x x x
76 reheat 1 hysteresis 0.0..10.0 K 0..100 x x x x x
77 reheat 2 start temperature 0.0..10.0 K 0..100 x x x x
78 reheat 2 hysteresis 0.0..10.0 K 0..100 x x x x
79 reheat 3 start temperature 0.0..10.0 K 0..100 x x x
80 reheat 3 hysteresis 0.0..10.0 K 0..100 x x x
81 PWW valve start temperature 0.0..10.0 K 0..100 x x x
82 PWW valve proportional band 0.0..10.0 K 0..100 x x x
83 dehumidification start 0..90% 0..90 x x x x x
84 dehumidification hysteresis 0..90% 0..90 x x x x x
85 humidification start 0..90% 0..90 x x x x x
86 humidification hysteresis 0..90% 0..90 x x x x x
87 humidification start (analogue) 0..90% 0..90 x x x x
88 humidification proportional band (analogue) 0..90% 0..90 x x x x
------------------------------------- d a t a m o d u l e 2 -----------------------------------------
89 compressor start (setpoint + val) 0.0..10.0 K 0..100 x x x x
90 compressor hysteresis 0.0..10.0 K 0..100 x x x x
91 suction valve start 0.0..10.0 K 0..100 x x x
92 suction valve proportional band 0.0..10.0 K 0..100 x x x
93 drycooler start temperature 0..45°C 0..45 x x x
94 reheat 1 start temperature 0.0..10.0 K 0..100 x x x x
95 reheat 1 hysteresis 0.0..10.0 K 0..100 x x x x
96 reheat 2 start temperature 0.0..10.0 K 0..100 x x x x
97 reheat 2 hysteresis 0.0..10.0 K 0..100 x x x x
98 reheat 3 start temperature 0.0..10.0 K 0..100 x x x
99 reheat 3 hysteresis 0.0..10.0 K 0..100 x x x
100 dehumidification start 0..90% 0..90 x x x x
101 dehumidification hysteresis 0..90% 0..90 x x x x
102 humidification start 0..90% 0..90 x x x x
103 humidification hysteresis 0..90% 0..90 x x x x
------------------------------------- d a t a m o d u l e 3 -----------------------------------------
104 compressor start (setpoint + val) 0.0..10.0 K 0..100 x x x x
105 compressor hysteresis 0.0..10.0 K 0..100 x x x x
106 suction valve start 0.0..10.0 K 0..100 x x x
107 suction valve proportional band 0.0..10.0 K 0..100 x x x
108 drycooler start temperature 0..45°C 0..45 x x x
109 reheat 1 start temperature 0.0..10.0 K 0..100 x x x x
110 reheat 1 hysteresis 0.0..10.0 K 0..100 x x x x
111 reheat 2 start temperature 0.0..10.0 K 0..100 x x x x
112 reheat 2 hysteresis 0.0..10.0 K 0..100 x x x x
113 reheat 3 start temperature 0.0..10.0 K 0..100 x x x