641
1A
www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright
©
2013 Eaton’s Crouse-Hinds Business
1A
PowerPlus
™
Panelboards
Power
EXD Series (Div. 1 & 2)
D2D Series (Div. 2)
EXD Series:
Cl. I, Div. 1 & 2, Groups B†, C, D
Cl. I, Zone 1 & 2, IIB + H
2†
Cl. II, Div. 1, Groups E, F, G
Cl. II, Div. 2, Groups F, G
Cl. III
NEMA/EEMAC 3, 4, 4X‡, 7B†CD, 9EFG, 12
D2D Series:
Cl. I, Div. 2, Groups B†, C, D
Cl. I, Zone 2, IIB + H
2†
Cl. II, Div. 2, Groups F, G
Cl. III
NEMA/EEMAC: 3, 4, 4X‡, 7B†CD, 12
PowerPlus
™
Series Panelboards provide
both premium factory-sealed and value
non-factory-sealed solutions for the
protection and distribution of lighting,
power, and heat tracing circuits. This panel
solution is designed, engineered, and
manufactured to be the industry’s safest
and most dependable panelboard for
hazardous area locations.
PowerPlus Premium and
Value Solutions
• Premium Solution: PowerPlus factory-
sealed panelboards are premium
panelboards that provide maximum
circuit flexibility with labor savings during
installation, operation, and maintenance,
and are accommodating for future
changes in the field (order with either “S”
or “A” in base part number). Panels are
pre-wired to maximum circuit capacity,
allowing for easy and safe replacement
or installation of components in the field,
while maintaining factory-sealed integrity.
• Value Solution: PowerPlus non-factory-
sealed panelboards are value
panelboards that offer maximum circuit
flexibility and many of the same features
and benefits of the PowerPlus premium
line. This value solution is provided
without terminal housing and factory
wiring of circuits (order with “N” in base
part number). The non-factory-sealed
solution reduces initial panelboard
material costs and requires field wiring to
circuit breakers and external seals to be
field-installed during installation.
Applications:
EXD and D2D PowerPlus
™
panelboards are
used:
• In areas made hazardous by the
continuous or abnormal presence of
flammable gases, vapors, and
combustible dusts
• In areas subject to weather, dampness,
and corrosion
• For branch power distribution and circuit
protection to motors, valves, pumps,
lighting, heat tracing, receptacles, etc.
• For indoor and outdoor applications in
petroleum refineries, chemical and
petrochemical plants, and other process
industry facilities where similar hazards
exist
• To accommodate up to 100 amp branch
loads (only 3 circuits), balance is up to
50 amps
Standard Materials and
Finishes:
• Circuit breaker enclosure body and
cover – copper-free aluminum
• Terminal housing – type 316L stainless
steel ("S") or copper-free aluminum ("A")
• Gasket – neoprene (cast aluminum
enclosure); foam-in-place (stainless steel
enclosure)
• Operating handles – copper-free
aluminum
• Operating shafts and bushings, cover
bolts, washers, hinges, breather/drain,
retractile springs – stainless steel
• Circuit breaker operators – EXD/D2D
Size F: copper-free aluminum; all other
types: non-metallic
• Lifting bracket – electrogalvanized cold
rolled steel
• Chassis – silver-plated copper
• Breather cap – Delrin
®
non-metallic
material
• Neutral and ground bar – tin-plated
aluminum
†Group B and IIB + H2 is standard on all PowerPlus panels, but requires special brackets to be installed on breakers to ensure long-term operability of circuit breakers.
To order with brackets installed at factory, add suffix -GB. For field installable kit, order EXD-GB-KIT for Sizes B, C, and D separately.
‡NEMA 4X rating is available when ordered with suffix S752 or S753.
Delrin
®
is a registered trademark of DuPont.
Certifications and
Compliances:
EXD Series:
• NEC/CEC:
Class I, Division 1 & 2, Groups B†, C, D
Class I, Zone 1 & 2, IIB + H
2†
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
• NEMA/EEMAC: 3, 4, 4X‡, 7B†CD,
9EFG, 12
• CSA Enc. 3, 4, 5
• UL Standard: 67, 1203
• cUL (to CSA Standard C22.2
Nos. 29 & 30)
• IP65
D2D Series (Division 2):
• NEC/CEC:
Class I, Division 2, Groups B†, C, D
Class I, Zone 2, IIB + H
2†
Class II, Division 2, Groups F, G
Class III
• NEMA/EEMAC: 3, 4, 4X‡, 7B†CD, 12
• CSA Enc. 3, 4, 5
• UL Standard: 67, 1203
• cUL (to CSA Standard C22.2
Nos. 29 & 30)
• IP65
EATON 授权经销商 华微科技(天津)有限公司
丁先生 18622336331