- 3 -
Digital/Analog module Voltage output Current output
Protection
Voltage output has short circuit protection, but a long period short
circuit may cause internal wire damage and current output break.
Connect to DVP-PLC
MPU in series
Connectable to the left side of MPU, numbered from 100 to 107
according to the position of module from the closest to farthest to
MPU.
Operation/storage
Operation: 0 ~ 55°C (temp.); 50 ~ 95% (humidity); pollution degree 2
Storage: -25 ~70°C (temp.); 5 ~ 95% (humidity)
Vibration/shock
immunity
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC
61131-2 & IEC 68-2-27 (TEST Ea)
Control Register
CR# Attrib. Register name Explanation
#0 O R Model name
System used, data length is 8 bits (b7 ~
b0). Model code = H’4401. User can read
the data from program to check if there is
I/O module.
#1 O R Firmware version
Display the current firmware version in
hex. For example: 1.0A means CR#1 =
H’010A.
#2 X R/W CH1 output mode setting
#3 X R/W CH2 output mode setting
#4 X R/W CH3 output mode setting
#5 X R/W CH4 output mode setting
Output mode: Default = H’0000.
Take CH1 for example:
Mode 0 (H’0000): Voltage output (10V)
Mode 1 (H’0001): Current output
(0~+20mA)
Mode 2 (H’0002): Current output
(+4~+20mA)
Mode 3 (H’0003): Voltage output (0V~10V)
Mode -1 (H’FFFF): All channels are
unavailable
#6 X R/W
The enabling function of table
output
Please refer to the table of CR#6 below for
detail. Default = H’0000
#7 X R/W Enable table output function
Bit 0~ bit 3 activate the table output
function on CH1 ~ CH4. Modifying the
parameters in output table during table
output process is not allowed.
0: Stop, 1: Run, Default = H’0000.
#8 X R/W Curves of table output function
Please refer to the table of CR#8 for detail.
Default = H’0000
#16 X R/W CH1 output signal value
#17 X
R/W
CH2 output signal value
#18 X
R/W
CH3 output signal value
#19 X
R/W
CH4 output signal value
Voltage output range: K-32,000~K32,000
Current output range: K0~K32,000
Default: K0
#20 X R/W
Present table output value of
CH1
#21 X
R/W
Present table output value of
CH2
#22 X
R/W
Present table output value of
CH3
#23 X
R/W
Present table output value of
CH4
Default = K32767