基于套管结构研究污垢热阻特性的方法与分析
刘潭白莉林英姿
(吉林建筑工程学院市政与环境工程学院,长春
130118 )
摘要:本实验采用套管结构模拟污水源热泵换热工况,流动在内管内侧的污水和流动在内管外侧的中介水(自来
水)进行对流换热.介绍了实验的装置和原理,并且分析了热阻的计算方法和实验误差的计算方法.
关键词:套管结构;温度;污垢热阻
中图分类号
:TK
172
文献标志码
:A
文章编号
:1009
-0185(2012)04
-00
另一
04
Method
and
Analysis of Researching Fouling Resistance
ßased
on the Double - pipe System
LIU
Tan, BAI
Li
,
LIN
Ying -
zi
(School
of
Municipal and Environmental Engineering, Jilin I
n.s
titute
of
Architecture and Civil Engineering,
Chα
ngchun
,
China 130118)
Abstract:
Th
is Method of double - pipe heat exchanger used simulating sewage water heat exchange conditions. The
sewage water
flow
in the inner tube and intermediary
(tap)
water
flow
in the annular tube. This paper gives the de-
vice and principle of double - pipe heat exchanger, and also analyzes the calculation method of thermal resistance
and
the experimental error.
Keywords:
the double - pipe system; temperature; fouling resistance
0
引言
污水中蓄含着大量的能量,污水源热泵系统是利用污水中热能的典范.然而,换热管管壁上生成的污垢
影响热能利用的效率,严重时会造成整个热泵系统的瘫痪.国内外的一些专家学者,从热力学角度对污垢特
性进行研究,试图找出污垢热阻随时间变化的规律;也有的学者试图从微观的角度研究污垢生长特性.但在
定量研究污垢热阻变化上至今没有质的突破.
污水源热泵系统中的换热器种类很多,主要有管壳式和板式换热器两种,实际工程中管壳式换热器应用
的最多.本实验采用套管结构模拟污水源热泵的管壳式换热器,并且按照实际工况运行,从而可以定量地分
析污垢的特性
[1]
1
动态监测污垢的实验装置
1.
1
实验装置
污垢热阻监测装置
[2]
主要由中介水(自来水)系统、污水系统和测控系统组成.
如图
1
所示,两根同轴的套管组成对流换热器,在内管流动的是污水,内管和外管间流动的是中介水,外
管规格
φ40mm
,内管
φ25
mm.
内、外管材质为钢管,长
4m
,
3.6m
,外管用保温材料包裹减少热损失.采用
精度为:t
O.l
"C的
pt
100
温度传感器测量温度,污水水箱的加热功率为
3
kW
,中介水的温度
O
"C
,污水温度
收稿日期
:2012
-04
-25.
作者简介:刘潭(1
989
仆,男,河北省郎郭市人,在读硕士研究生.