This manual contains text, diagrams and explanations which will guide the reader in the correct
installation, safe use and operation of the FX
2N
-10PG PULSE GENERATOR BLOCK and should be read
and understood before attempting to install or use the unit. Further information can be found in the
manuals listed under further information.
Specifications are subject to change without notice
Guidelines for the Safety of the User and Protection of FX
2N
-10PG
PULSE GENERATOR BLOCK
This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer using the product associated with this manual, should be of a competent nature, trained and
qualified to the local and national standards. These engineers should be fully aware of all aspects of safety with
regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to the local and
national standards.
c) All operators of the completed equipment should be trained to use that product in a safe and coordinated
manner in compliance to established safety practices.
Note:
The term ‘completed equipment’ refers to a third party constructed device which contains or uses
the product associated with this manual.
Note’s on the Symbols Used in this Manual
At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger
WILL
cause physical and property damage.
2) Indicates that the identified danger could
POSSIBLY
cause physical and property damage.
• Under no circumstances will Mitsubishi Electric be liable responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
• All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the
productbased on these illustrative examples.
• Owing to the very great variety in possible application of this equipment, you must satisfy yourself as
to its suitability for your specific application.
Further Information Manual Lists
Manual name Manual No. Description
FX
2N
-10PG
USER’S MANUAL
JY992D93401
Describes specifications, wiring, installation, handling,
etc. of FX
2N
-10PG. (Schedule in February, 2001.)
FX
2N
HARDWARE MANUAL
JY992D66301
Describes contents related to hardware of FX
2N
series
PLC such as specifications, wiring and installation.
FX
3U
Series
User’s Manual
- Hardware Edition
JY997D16501
Describes the specification, wiring and installation of
FX
3U
series PLC.
FX
2NC
HARDWARE MANUAL
JY992D76401
Describes contents related to hardware of FX
2NC
series
PLC such as specifications, wiring and installation.
FX
3UC
Series
User’s Manual
- Hardware Edition
JY997D28701
Describes the specification, wiring and installation of
FX
3UC
series PLC.
FX SERIES
PROGRAMMING
MANUAL
ΙΙ
JY992D88101
Describes instructions of FX
1S
/FX
1N
/FX
2N
/FX
2NC
series
PLC
FX
3U
/FX
3UC
Series
Programming Manual
- Basic & Applied
Instruction Edition
JY997D16601
This manual explains the installations of FX
3U
/FX
3UC
series PLC.
1. Introduction
The FX
2N
-10PG pulse generator block (Hereafter referred to as "FX
2N
-10PG" or "pulse generator block")
outputs pulses of 1MHz or less. It is a special function block to drive amplifiers for servo motors or stepper
motors. It is connected to an FX
2N
/FX
2NC
/FX
3U
/FX
3UC
series Programmable controller (Hereafter referred
to as "PLC") and used.
1.1 Features of the FX
2N
-10PG
1) Positioning control with a stepper motor or servo motor.
(1 FX
2N
-10PG can control 1 positioning axis.)
2) Can be connected to an FX
2N
/FX
2NC
/FX
3U
/FX
3UC
series PLC.
Data is read/written using FROM/TO instructions.
3) Pulses at up to 1MHz can be output.
1.2 External Dimensions and Each Part Name
Dimensions: mm (inches) MASS (Weight): Approx. 0.2kg (0.44 lbs)
Accessory: Special block No. label
a) Extension cable and connector
b) Mounting hole 2-
φ
4.5(0.18inch)
c) Extension port
d) I/O port
e) DIN rail clip
f) Attachment groove for 35mm(1.38inch)wide DIN rail
80(3.15)
43(1.68)
POWER
ERROR
FP
PGO
RP
f
B
fA
START
CLR
DOG
X1
X0
87(3.43)
74(2.91)
FX
2N
-10PG
90(3.54)
4(0.16)
c)
d)
e)
b)a)
f)
2-f
4.5(0.18)
1.3 LED display
1.4 Array and allocation of pin
LED name State Content of display
POWER
OFF No 5V DC power from PLC main unit by way of the extension cable.
Lit 5V DC is fed from the PLC main unit by way of the extension cable.
START
OFF START input OFF.
Lit START input ON.
ERROR
OFF Normal operation.
Blinking Error has occurred.
Lit CPU error
FP
OFF Forward pulse or pulses not output.
Blinking Forward pulse or pulses output.
RP
OFF Reverse pulse or direction command not output.
Blinking or lit Reverse pulse or direction command output.
CLR
OFF CLR signal idle.
Lit CLR signal output (It completes Home position return).
DOG
OFF DOG input OFF.
Lit DOG input ON.
PG0
OFF Zero point signal input OFF.
Lit Zero point signal input ON.
φ
A
OFF A phase input of manual pulse generator OFF.
Blinking A phase input of manual pulse generator ON.
φ
B
OFF B phase input of manual pulse generator OFF.
Blinking B phase input of manual pulse generator ON.
X0,X1
OFF Interrupt input OFF.
Lit Interrupt input ON.
Terminal
name
Content
VIN+
Power supply input terminal for pulse output
(5 to 24V DC)
FP+
• Forward/reversal mode
Forward pulse output terminal
• Pulse/direction mode
Pulse output terminal
RP+
• Forward/reversal mode
Reversal pulse output terminal
• Pulse/direction mode
Direction output terminal
PG0+ Zero point signal input terminal
CLR+
Output terminal to clear collecting deflection
counter pulse of servo amplifier
φ
A+
A phase input terminal of manual pulse
generator
φ
B+
B phase input terminal of manual pulse
generator
DOG DOG input terminal
S/S
Power supply input terminal
(START,DOG,X0,X1) (24V DC)
Pins (S/S) are short-circuited internally
X0 Interruption input terminal
VIN- Common terminal for VIN+
FP- Common terminal for FP+
RP- Common terminal for RP+
PG0- Common terminal for PG0 +
CLR- Common terminal for CLR+
φ
A-
Common terminal of A phase input for manual
pulse generator
φ
B-
Common terminal of B phase input for manual
pulse generator
START START input terminal