- 3 -
#1: Life curves
Contact
Current(A)
0.5
0.1
0.2
50
0.3 0.7
12
200
300
500
100
1000
2000
3000
O
p
e
r
a
t
i
o
n
(
X
1
0
)
3
120VAC Resistive
30VDC Inductive(t=7ms)
240VAC Inductive(cos 0.4)
ψ
=
120VAC Inductive(cos =0.4)
ψ
30VDC
Inductive
( t=4 0ms )
[ Figure 3 ]
Digital Input/Output Modules
Input unit Output unit
Model Power
Points Type Points Type
DVP08HM11N 8 0
DVP16HM11N 16 0
DVP32HM11N 32 0
N/A
DVP08HN11R 0 8
DVP08HP11R 4 4
DVP16HP11R 8 8
Relay: 250VAC/30VDC
2A/1point
DVP08HN11T 0 8
DVP08HP11T 4 4
DVP16HP11T
24VDC
8 8
Transistor: 5 ~ 30VDC
0.3A/1point at 40°C
DVP32HN00R 0 32
DVP32HP00R 16 16
DVP48HP00R 24 24
Relay: 250VAC/30VDC
2A/1point
DVP32HN00T 0 32
DVP32HP00T 16 16
DVP48HP00T
100 ~ 240V
AC
24
DC Type
Sink/Source
24
Transistor: 5 ~ 30VDC
0.3A/1 point at 40°C
Installation
Please install the PLC in an enclosure with sufficient space
around it to allow heat dissipation, as shown in the figure.
y Direct Mounting: Please use M4 screw according to the
dimension of the product.
y DIN Rail Mounting: When mounting the PLC to 35mm DIN
rail, be sure to use the retaining clip to stop any side-to-side movement
of the PLC and reduce the chance of wires being loose. The retaining
clip is at the bottom of the PLC. To secure the PLC to DIN rail, pull
down the clip, place it onto the rail and gently push it up. To remove the
PLC, pull the retaining clip down with a flat screwdriver and gently
remove the PLC from DIN rail, as shown in the figure.
Wiring
1. Use O-type or Y-type terminal. See the figure in the
right hand side for its specification. PLC terminal
screws should be tightened to 9.50 kg-cm (8.25 in-Ibs)
and please use only 60/75ºC copper conductor.
To s u it M3 . 5
screw terminals
Below
6.2 mm
Below
6.2 mm