电气试验田 http://sora.blog.dianyuan.com
美国西部电网 WSCC 三机九节点系统
基准值取 S
B
=100MVA,U
B
=230kV,系统频率为 60Hz。
发电机参数:
G1 : 247.5MVA , 16.5kV , 功 率 因 数 为 1 , 水 轮 机 组 ( Salient-
Pole ) , 180rpm , x
d
=0.146 , x'
d
=0.0608 , x
q
=0.0969 , x'
q
=0.0969 , x
l
=0.0336 , T'
d0
=8.96s , T'
q0
=0s ,
H=23.64s,D=0
G2 : 192MVA , 18kV , 功 率 因 数 为 0.85 , 汽 轮 机 组 ( Round-
Rotor), 3600rpm,x
d
=0.8958,x'
d
=0.1198,x
q
=0.8645,x'
q
=0.1969,x
l
=0.0521,T'
d0
=6s,T'
q0
=0.535s,
H=6.4s,D=0
G3 : 128MVA , 13.8kV , 功 率 因 数 为 0.85 , 汽 轮 机 组 ( Round-
Rotor), 3600rpm,x
d
=1.3125,x'
d
=0.1813,x
q
=1.2578,x'
q
=0.25,x
l
=0.0742,T'
d0
=5.89s,T'
q0
=0.6s,H=
3.01s,D=0
变压器参数:
T1:16.5/230kV,X
T
=0.0576;T2:18/230kV,X
T
=0.0625;T3:13.8/230kV,X
T
=0.0586
线路参数:
Line1 : Z=0.01+j0.085 , B/2=j0.088 ; Line2 : Z=0.032+j0.161 , B/2=j0.153 ; Line3 :
Z=0.017+j0.092 , B/2=j0.079 ; Line4 : Z=0.039+j0.17 , B/2=j0.179 ; Line5 :
Z=0.0085+j0.072,B/2=j0.0745;Line6:Z=0.0119+j0.1008,B/2=j0.1045
负荷 LumpA:125+j50MVA,LumpB:90+j30MVA,LumpC:100+j35MVA
将发电机 G1 设为系统的平衡节点(Slack),设置电压幅值为 1.04pu,电压参考相角为 0°;将 G2
和 G3 设为 PV 节点,分别设置有功出力为 1.63pu 和 0.85pu,设置电压幅值都为 1.025pu。